- AC distributionThree-phase, four-wire wye; 400/230 V · 50 Hz is also modeled
- 480/277 V · 60 Hz
- UPS operating modeInput, rectifier, DC link, inverter, AC distribution; bypass energized and unloaded
- Double conversion
- UPS DC linkTwo-wire +/− with PE; floating IT; no neutral
- 800 VDC pole-to-pole
- TopologySix inverter sections per path; no DC tie between A and B
- Independent A / B
- Bus continuous limitVerify installation derating
- 4,000 A per bus
- Tap-off continuous limit12 monitored feeders in 6 pairs
- 800 A per feeder
- RectifiersN+1 allowance of 3.2 MW, also limited by bus ampacity
- 9 × 400 kW per path
- Redundant bus capacityOne surviving path, out of 6.4 MW installed across both
- 3.2 MW
- AC power-quality meters5 locations on each of 2 paths
- 10
- DC power meters2 DC mains and 12 inverter feeds
- 14
- Thermal channels12 joints and 4 conductor channels
- 16
- Insulation monitorsOne on each isolated bus
- 2
- Residual-current sensorsDC-capable; AC+DC RMS
- 2