SmartDCDC-01 / Data hall 01 / DC electrical217:46:54 ETDemo dataProduct overview

DC electrical

2 active alarms
Measurement guide

Bus voltage, current, DC ripple and captured disturbances.

DC bus input power1.74MWA + B buses · positive import
Highest bus loading27.3%Of 4,000 A per path
Highest voltage ripple0.200%RMS ripple / DC mean
15-minute demand1.75MWA + B buses · rolling average

DC measurements

Per-bus quantities · independent A and B paths

PE is a voltage reference, not a load return. On a floating two-wire system, pole-to-earth voltages can shift while pole-to-pole voltage stays normal. Sampled 5-minute extrema exclude fast transients: the capture below records a 772.4 V minimum that they never see.
DC · 2 wire
MeasurementBus ABus BUnit
Pole-to-pole voltageDC mean, + conductor to − conductor800.2800.2V DC
Positive pole to PESigned voltage to protective earth+410.9+399.5V DC
Negative pole to PESigned voltage to protective earth-389.2-400.6V DC
Deviation from nominal(Measured voltage − 800 V) / 800 V+0.02+0.02%
Lowest 5-min mean voltageNormal-operation minimum · 24-hour historian799.715:30 ET799.317:50 ETV DC
Highest 5-min mean voltageNormal-operation maximum · 24-hour historian800.900:30 ET800.522:35 ETV DC
Mean bus currentOne DC path, positive toward load1,093.91,080.4A DC
Total RMS current√(I DC² + I ripple RMS²), derived1,093.91,080.4A RMS
Peak 5-min mean current24-hour historian; not a fast event peak1,226.708:45 ET1,225.108:45 ETA DC
Parallel-conductor sharingNeeds individual conductor sensorsNot instrumentedNot instrumentedA / %
DC powerSteady-state, V DC × I DC875.3864.5kW
Bus loading4,000 A continuous limit assumed27.327.0%
15-minute demandRolling average · simulated historian873.3872.1kW
Peak 15-minute demandMaximum in the 24-hour record979.9977.4kW

PE is a voltage reference, not a load return. On a floating two-wire system, pole-to-earth voltages can shift while pole-to-pole voltage stays normal. Sampled 5-minute extrema exclude fast transients: the capture below records a 772.4 V minimum that they never see.

Ripple & power quality

AC component on top of the DC bus

The acquisition specification, with anti-alias filtering. Hardware sets the effective bandwidth and accuracy, and the dashboard refresh is separate from waveform sampling.
MeasurementBus ABus BUnit
Voltage ripple RMSAC component after removing DC mean1.601.30V RMS
Voltage ripple peak-to-peakMax − min of filtered capture8.407.10V p-p
Voltage ripple factor100 × ripple RMS / |DC mean|0.2000.162%
Current ripple RMSAC component · DC-capable sensor3.83.1A RMS
Current ripple factor100 × ripple RMS / |DC mean|0.350.29%
Design bandwidth
10 Hz–20 kHz
Capture window
100ms
Acquisition target
100kS/s
Result aggregate
1s

The acquisition specification, with anti-alias filtering. Hardware sets the effective bandwidth and accuracy, and the dashboard refresh is separate from waveform sampling.

Distribution loss & efficiency

A + B buses · bus input to outgoing feeder meters

Loss is bus-input power minus summed feeder-output power. This boundary excludes rectifier conversion losses, and small real losses need synchronized meters with suitable uncertainty.
Derived
Bus input
1,739.81kW
Feeder output
1,738.09kW
Distribution loss
1.72kW
Efficiency
99.90%

Loss is bus-input power minus summed feeder-output power. This boundary excludes rectifier conversion losses, and small real losses need synchronized meters with suitable uncertainty.

Fast event capture

Triggered local recorder · separate from dashboard polling

Recorded minimum
772.4V
Duration below 780 V
12.4ms
Capture location
Bus A input
Sample event ID
EVT-A-1042
760 V780 V800 V-10 ms0 ms10 ms20 ms

Relative trigger time · Shaded band is the 12.4 ms below 780 V · Recovered, record retained

Measurement context

Definitions that travel with the data

DC ripple percentages are not AC THD. Frequency, power factor and reactive power belong to the AC meters. Displayed DC power is a steady-state V × I; real DC power uses synchronized voltage and current samples, and fast events and ripple need a local recorder with the stated bandwidth.
Power-flow signPositive means source toward DC load
Import +
Actual active powerMean of simultaneous instantaneous v(t) × i(t)
mean(v · i)
Displayed DC powerSteady-state averages; ripple power correlation omitted
V DC × I DC
Event record requirementsTrigger, extrema, duration, dV/dt, dI/dt, pre/post waveform
Quality and provenanceSample time, validity, clock sync and measurement window

DC ripple percentages are not AC THD. Frequency, power factor and reactive power belong to the AC meters. Displayed DC power is a steady-state V × I; real DC power uses synchronized voltage and current samples, and fast events and ripple need a local recorder with the stated bandwidth.