SmartDCDC-01 / Data hall 01 / UPS DC overview217:46:53 ETDemo dataProduct overview

UPS DC overview

2 active alarms
Measurement guide

The DC link between your rectifier, battery and inverter sections.

Total DC bus power1.743MWAcross A + B · positive toward load
Bus A voltage800.1VDCBus B 800.2 VIn range
Highest bus loading27.4%A 1,096 A · B 1,082 A · 4,000 A per bus
Hottest valid connection61.6°CJ04-A · +33.2 K riseAdvisory

UPS DC distribution

Independent DC links · 6 inverter sections per path

  • Bus A
  • Bus B
Source ARectifier · 9/9 onlineBESS 94% · standby
Bus A800.1 VDC1,096 A0.877 MW27.4% loaded
INV-A01142 kW DC
INV-A02152 kW DC
INV-A03147 kW DC
INV-A04164 kW DC
INV-A05131 kW DC
INV-A06141 kW DC
INV-B01138 kW DC
INV-B02148 kW DC
INV-B03147 kW DC
INV-B04160 kW DC
INV-B05132 kW DC
INV-B06139 kW DC
Source BRectifier · 9/9 onlineBESS 92% · standby
Bus B800.2 VDC1,082 A0.866 MW27.1% loaded
  • Breaker closed
  • Breaker open
  • Thermal advisory
  • Power flow

Click a tap-off to inspect · Functional one-line · Each route represents a +/− pair · No bus tie · Separate A / B inverters

Power demand

Historical trend · Eastern time

  • Bus A
  • Bus B
0.850.8750.90.9250.9511:4513:4515:5017:46MW

15-minute demand 1.745 MW · 24-hour import 44.33 MWh

Tap-off feeders

DC feeds to inverter sections

FeederVoltageCurrentPowerLoadingJoint temp.
Section 01799.4 V178 A141.9 kW22.2%42.5 °C
Section 01799.6 V173 A138.4 kW21.6%41.8 °C
Section 02799.3 V190 A151.6 kW23.7%44.8 °C
Section 02799.5 V186 A148.3 kW23.2%43.2 °C
Section 03799.5 V183 A146.7 kW22.9%43.4 °C
Section 03799.4 V184 A147.1 kW23.0%43.0 °C
Section 04798.9 V205 A163.6 kW25.6%61.6 °C
Section 04799.3 V200 A160.0 kW25.0%46.1 °C
Section 05799.4 V164 A131.2 kW20.5%41.8 °C
Section 05799.5 V165 A132.0 kW20.6%43.6 °C
Section 06799.2 V176 A141.0 kW22.1%45.4 °C
Section 06799.4 V174 A139.3 kW21.8%Stale

12 of 12 feeders shown · 800 A configured continuous limit

Protection & resilience

Electrical health at a glance

Monitoring
Minimum insulation
1.82MΩ

IMD measurement valid

Maximum residual · AC+DC
14.2mA

RMS · DC–1 kHz band

Surviving-path utilization54.5%Facility 2N model · after A or B loss1.46 MW margin