SmartDCUPS DC overview
The DC link between your rectifier, battery and inverter sections.
Total DC bus power1.743MWAcross A + B · positive toward load
Bus A voltage800.1VDCBus B 800.2 VIn range
Highest bus loading27.4%A 1,096 A · B 1,082 A · 4,000 A per bus
Hottest valid connection61.6°CJ04-A · +33.2 K riseAdvisory
UPS DC distribution
Independent DC links · 6 inverter sections per path
- Bus A
- Bus B
Source ARectifier · 9/9 onlineBESS 94% · standby
INV-A01142 kW DC
INV-A02152 kW DC
INV-A03147 kW DC
INV-A04164 kW DC
INV-A05131 kW DC
INV-A06141 kW DC
INV-B01138 kW DC
INV-B02148 kW DC
INV-B03147 kW DC
INV-B04160 kW DC
INV-B05132 kW DC
INV-B06139 kW DC
Source BRectifier · 9/9 onlineBESS 92% · standby
- Breaker closed
- Breaker open
- Thermal advisory
- Power flow
Click a tap-off to inspect · Functional one-line · Each route represents a +/− pair · No bus tie · Separate A / B inverters
Power demand
Historical trend · Eastern time
- Bus A
- Bus B
MW
15-minute demand 1.745 MW · 24-hour import 44.33 MWh
Tap-off feeders
DC feeds to inverter sections
| Feeder | Voltage | Current | Power | Loading | Joint temp. |
|---|---|---|---|---|---|
| Section 01 | 799.4 V | 178 A | 141.9 kW | 22.2% | 42.5 °C |
| Section 01 | 799.6 V | 173 A | 138.4 kW | 21.6% | 41.8 °C |
| Section 02 | 799.3 V | 190 A | 151.6 kW | 23.7% | 44.8 °C |
| Section 02 | 799.5 V | 186 A | 148.3 kW | 23.2% | 43.2 °C |
| Section 03 | 799.5 V | 183 A | 146.7 kW | 22.9% | 43.4 °C |
| Section 03 | 799.4 V | 184 A | 147.1 kW | 23.0% | 43.0 °C |
| Section 04 | 798.9 V | 205 A | 163.6 kW | 25.6% | 61.6 °C |
| Section 04 | 799.3 V | 200 A | 160.0 kW | 25.0% | 46.1 °C |
| Section 05 | 799.4 V | 164 A | 131.2 kW | 20.5% | 41.8 °C |
| Section 05 | 799.5 V | 165 A | 132.0 kW | 20.6% | 43.6 °C |
| Section 06 | 799.2 V | 176 A | 141.0 kW | 22.1% | 45.4 °C |
| Section 06 | 799.4 V | 174 A | 139.3 kW | 21.8% | Stale |
12 of 12 feeders shown · 800 A configured continuous limit
Protection & resilience
Electrical health at a glance
Monitoring
- Minimum insulation
- 1.82MΩ
- Maximum residual · AC+DC
- 14.2mA
IMD measurement valid
RMS · DC–1 kHz band
Surviving-path utilization54.5%Facility 2N model · after A or B loss1.46 MW margin