SmartDCMeasurement library
AC power quality and UPS DC monitoring, with how each value is measured.
99 of 99 measurements
99 measurements across 15 disciplines
Measured, derived, status and configured values
Which measurements apply depends on the sensors fitted at a given site. Cadences are design targets.| Measurement | ID | Type | Unit | Instrument | Definition | Cadence |
|---|---|---|---|---|---|---|
| Pole-to-pole DC voltageVoltage | V01 | Measured | V DC | Isolated DC voltage input | Mean voltage between positive and negative conductors at each main bus and feeder. The nominal system value is 800 V pole-to-pole. | 1 s aggregate; 2 s display |
| Positive pole to PEVoltage | V02 | Measured | V DC | High-impedance isolated voltage input | Signed positive-conductor potential relative to protective earth. On a floating IT system this may drift; it is not a regulated +400 V rail. | 1 s aggregate; 2 s display |
| Negative pole to PEVoltage | V03 | Measured | V DC | High-impedance isolated voltage input | Signed negative-conductor potential relative to protective earth. Together with positive-to-PE voltage, reveals displacement of the floating system. | 1 s aggregate; 2 s display |
| Voltage minimum and maximumVoltage | V04 | Measured | V DC · time | DC meter extrema registers | Lowest and highest pole-to-pole voltage in the selected period, with timestamps and the meter aggregation interval. Separate from waveform event extrema. | 1 s extrema; retained history |
| Distribution voltage dropVoltage | V05 | Derived | V · % | Synchronized upstream/downstream meters | Upstream voltage minus feeder-end voltage; percent drop uses upstream voltage. Compare time-aligned readings under stable load and account for meter uncertainty. | 1 s calculation |
| Pole-to-earth displacementVoltage | V06 | Derived | V DC | Signed pole-to-PE voltage inputs | Common-mode potential = (Vpositive-to-PE + Vnegative-to-PE) / 2. Diagnostic only; a balanced value does not prove healthy insulation. | 1 s calculation |
| Signed main-bus currentCurrent | I01 | Measured | A DC | DC-rated Hall, zero-flux or isolated shunt sensor | Current through each independent bus. Positive denotes source-to-load flow; negative denotes reverse flow. Do not sum outgoing and returning conductor magnitudes as load current. | 1 s aggregate; 2 s display |
| Signed feeder currentCurrent | I02 | Measured | A DC | DC sensor at every monitored tap-off | Branch current for each rack or zone. Retain the circuit rating and polarity convention alongside the measurement. | 1 s aggregate; 2 s display |
| Parallel conductor currentCurrent | I03 | Measured | A DC | Individual DC sensors on parallel conductors | Current in each parallel positive or negative conductor where sensors are fitted. Supports identification of uneven sharing and overloaded individual paths. | 1 s aggregate |
| Parallel conductor sharing errorCurrent | I04 | Derived | % | Time-aligned parallel conductor current inputs | 100 × maximum absolute deviation from the mean conductor current / absolute mean current, calculated for parallel conductors of the same pole. Suppress near zero load. | 1 s calculation |
| Peak current and event timestampCurrent | I05 | Measured | A · time | DC meter peak register / waveform recorder | Highest current with capture interval and timestamp. High-speed event peaks are distinct from peaks of slow display aggregates. | Event capture plus 1 s aggregate |
| Signed DC active powerPower & energy | P01 | Measured | kW | Synchronized DC power meter | Mean of simultaneous instantaneous voltage × current samples. Positive is import to the load. Mean voltage × mean current is only a steady-state approximation when ripple correlation is negligible. | 1 s meter aggregate |
| 15-minute rolling demandPower & energy | P02 | Derived | kW | Meter or historian | Average imported power over a rolling 15-minute window ending at each 5-minute sample boundary. The dashboard uses rolling demand rather than fixed demand blocks. | Recalculate at 5 min sample boundaries |
| Maximum 15-minute rolling demandPower & energy | P03 | Derived | kW · time | Historian demand archive | Largest rolling 15-minute demand in the selected period, evaluated at 5-minute sample boundaries, with interval start and end timestamps. Independent per-path maxima must not be added. | Evaluate at 5 min sample boundaries |
| Imported energyPower & energy | P04 | Measured | kWh | DC energy meter import register | Time integral of positive active power. Keep cumulative, interval and daily totals distinct, with reset/rollover handling. | 1 min history; 2 s display |
| Exported energyPower & energy | P05 | Measured | kWh | DC energy meter export register | Time integral of negative active power, reported as a positive exported-energy quantity. Do not hide reverse energy inside a net-only register. | 1 min history; 2 s display |
| Bus and feeder utilizationPower & energy | P06 | Derived | % · A spare | Current inputs plus approved operating limits | Absolute current divided by the applicable continuous operating limit. A configured nameplate rating is not automatically the allowable installed operating limit. | 1 s calculation |
| Distribution loss and efficiencyPower & energy | P07 | Derived | kW · % | Synchronized input/output DC power meters | Loss = input power minus summed downstream power, adjusted for storage and other branches. Efficiency = output/input. Flag results below combined meter uncertainty. | 1 min average |
| AC-component voltage ripple RMSDC quality | Q01 | Measured | V RMS | Isolated waveform analyzer | RMS of v(t) minus its DC mean. Always retain the measurement bandwidth, window and sample rate; example design band is 10 Hz–20 kHz. | 1 s result; ≥100 kS/s acquisition |
| Voltage ripple peak-to-peakDC quality | Q02 | Measured | V p-p | Isolated waveform analyzer | Maximum minus minimum AC-component voltage over the stated capture window and bandwidth. Not interchangeable with RMS ripple. | 1 s result; ≥100 kS/s acquisition |
| Voltage ripple factorDC quality | Q03 | Derived | % | Ripple RMS and DC voltage inputs | 100 × AC-component voltage RMS / absolute DC mean voltage, using the same observation interval. State the bandwidth and suppress near zero DC voltage. | 1 s calculation |
| AC-component current ripple RMSDC quality | Q04 | Measured | A RMS · % | DC-capable current sensor plus waveform analyzer | RMS of current after removing its DC mean, with declared bandwidth. Relative ripple uses absolute mean current and is invalid near zero current. | 1 s result; ≥100 kS/s acquisition |
| Sag, swell and interruption capturesDC quality | Q05 | Measured | V · ms · count | Triggered voltage/current waveform recorder | Event type, threshold, start time, duration, minimum/maximum and pre/post-trigger waveform. Event duration comes from local fast acquisition, never inferred from 2-second dashboard polling. | Hardware-triggered event capture |
| Voltage slew rateDC quality | Q06 | Derived | V/ms | Filtered high-speed voltage waveform | Maximum and minimum dV/dt over a specified event window. Derivative results must include sample interval and filtering to avoid presenting noise as a transient. | Triggered waveform calculation |
| Current slew rateDC quality | Q07 | Derived | A/ms | Filtered high-speed current waveform | Maximum and minimum dI/dt with capture interval, sensor bandwidth and filter settings. Useful for dynamic load and fault-event diagnostics. | Triggered waveform calculation |
| Joint and conductor temperatureThermal | T01 | Measured | °C | Installed contact sensors / calibrated IR system | Positive and negative bar joints, terminations and conductor temperatures with location identifiers. IR measurements require valid emissivity and line-of-sight assumptions. | 5 s acquisition |
| Local ambient temperatureThermal | T02 | Measured | °C | Ambient sensor near each monitored enclosure | Local air temperature paired with each thermal zone. Use it to distinguish high room temperature from local connection heating. | 5 s acquisition |
| Temperature rise above ambientThermal | T03 | Derived | °C rise | Joint and matching ambient sensors | Joint temperature minus local ambient temperature using aligned readings. Operating limits depend on the approved equipment, insulation and installation. | 5 s calculation |
| Temperature rate of riseThermal | T04 | Derived | °C/min | Temperature historian | Slope over a specified recent window, such as five minutes, with concurrent current/loading trend. A fast rise can matter before an absolute limit is reached. | 1 min calculation |
| Connection voltage dropThermal | T05 | Measured | mV | Isolated differential input across instrumented joint | Small differential voltage across a defined connection under load. Measurement must tolerate the bus common-mode voltage and use suitable isolation. | 1 s aggregate |
| Estimated connection resistanceThermal | T06 | Derived | µΩ | Joint mV drop and matching current sensor | R = 1000 × joint voltage drop in mV / current in A. Valid only at sufficient, stable current after offset compensation; this is an online estimate, not an offline micro-ohmmeter test. | 1 min stable-load estimate |
| Estimated connection heating lossThermal | T07 | Derived | W | Estimated joint resistance and RMS current | Approximate resistive loss = I RMS squared × R. With R in µΩ divide by 1,000,000. Distinguish this local estimate from metered whole-path losses. | 1 min stable-load estimate |
| System insulation resistanceInsulation | G01 | Measured | MΩ | Insulation monitoring device for floating IT DC | Effective resistance of the connected active system to PE. Trend each independent bus and retain response time, self-test status and lowest recorded value. | Native IMD update; display age explicitly |
| Pole-specific insulation estimateInsulation | G02 | Derived | MΩ | Compatible IMD diagnostic registers, if available | Positive-to-PE and negative-to-PE estimates only if the selected IMD provides valid pole-specific data. Never infer an exact insulation resistance from pole voltage alone. | Native device update; otherwise N/A |
| System leakage capacitanceInsulation | G03 | Measured | µF | Compatible IMD capacitance measurement | Connected system capacitance to PE. It affects insulation-monitor response and fault behavior; retain the IMD permitted capacitance and response characteristics. | Native IMD update |
| Residual / earth-leakage currentInsulation | G04 | Measured | mA DC / RMS | DC-capable zero-flux residual sensor | Residual current around all active conductors, with bandwidth and DC/RMS basis stated. On a floating system this complements the IMD; it does not replace insulation-resistance monitoring. | 1 s aggregate; local event detection |
| IMD health and connection statusInsulation | G05 | Status | state · time | IMD self-test and connection monitoring | Device healthy/fault, test result and measuring-lead continuity. If buses are coupled, coordinate IMDs according to the approved architecture; do not assume independent monitors can operate on one connected system. | Device event; 2 s status poll |
| Located insulation faultInsulation | G06 | Status | circuit · state | Compatible insulation-fault location system | Identified feeder, locator confidence/status and event time when a fault-locator is installed. Show Not instrumented if unavailable; residual current alone does not prove the location of an IT insulation fault. | Native locator scan / event |
| Breaker position and trip stateProtection | R01 | Status | state | Independent breaker auxiliary/trip contacts | Closed, open, tripped or unknown for every main and branch device. Distinguish position feedback from commands and from current flowing through the circuit. | Event-driven; 2 s display |
| Trip cause and sequence of eventsProtection | R02 | Status | cause · time | Protection relay / trip-unit event record | Latched cause, trip timestamp, operation sequence and captured fault data where supported. Preserve acknowledged versus cleared states and source timestamp quality. | Device event; source resolution retained |
| Protection and trip circuit healthProtection | R03 | Status | state | Trip-unit diagnostics and supervision contacts | Trip-unit healthy, auxiliary supply healthy and trip-circuit continuity where supervised. No status may be labelled healthy when the channel is stale or absent. | Device event; 2 s status poll |
| DC device ratingsProtection | R04 | Configured | V DC · A · kA | Approved manufacturer nameplate and coordination study | Rated DC voltage/current and applicable interrupting/withstand ratings, with required pole configuration and conditions. These are engineering metadata, not measured fault current or a live safety margin. | Engineering change control |
| Protection and alarm settingsProtection | R05 | Configured | A · V · ms · °C · MΩ | Approved device settings / alarm configuration | Pickup, time delay, hysteresis, latching and reset rules, separately identifying hardware protection and dashboard alarms. Example dashboard thresholds are not approved equipment settings. | Engineering change control |
| Fuse, contactor, precharge and SPD healthProtection | R06 | Status | state | Instrumented auxiliary contacts and controller registers | Show each fitted fuse alarm, contactor position, precharge ready/fault and surge protective device condition separately. Use Not instrumented for devices without feedback. | Event-driven; 2 s status poll |
| Arc detection statusProtection | R07 | Status | state · time | Qualified DC arc detection system, if fitted | Detector health and alarm record only where an appropriate detector is installed. An absent alarm, normal bus telemetry or dashboard status cannot establish absence of arcing. | Detector event; otherwise Not instrumented |
| Rectifier module availabilitySources | S01 | Status | online / total · state | Rectifier controller | Available, failed, standby and current-limited modules, including controller health. Available output capacity must reflect failed modules and operating derating. | Event-driven; 2 s poll |
| Rectifier current sharingSources | S02 | Derived | A / module · % | Rectifier per-module DC current registers | Individual module output currents and maximum deviation from the mean among active modules. Evaluate at sufficient load and account for differing module ratings. | 1 s aggregate |
| Rectifier conversion efficiencySources | S03 | Derived | % | Synchronized AC input and DC output power meters | 100 × DC output active power / AC input active power over the same interval. AC power quality belongs to the upstream meter view; it is not a DC bus measurement. | 1 min average |
| Battery state of chargeSources | S04 | Derived | % | Battery management system estimate | BMS-reported remaining charge fraction with data age and BMS estimation quality. State of charge is an estimate, not a direct guarantee of available runtime. | Native BMS update; 5 s display |
| Battery state of healthSources | S05 | Derived | % | Battery management system estimate | BMS-reported health using the manufacturer definition and reference capacity. Track test date and estimator availability. | Native BMS update |
| Battery power and discharge limitSources | S06 | Measured | kW · A | BMS / DC-DC converter and battery DC meter | Signed charge/discharge power and current, permitted discharge power/current, temperature derating and contactor readiness. Show polarity convention explicitly. | 1 s aggregate; native limit update |
| Usable battery energy and runtimeSources | S07 | Derived | kWh · min | BMS, approved reserve policy and load metering | Estimated runtime = bus-side usable energy / protected load × 60. Apply conversion efficiency only if energy is specified upstream of the converter. BMS discharge limits and actual contingency load still apply. | 5 s estimate |
| Battery cell and temperature extremaSources | S08 | Measured | V · mV · °C | BMS cell-level telemetry | Lowest/highest cell voltage, cell spread, hottest/coldest temperature and sensor location. Include BMS warning and fault states. | Native BMS update; 5 s display |
| Independent path availabilitySources | S09 | Status | A/B state | Source, breaker and distribution status model | Availability of each complete source-to-load path, including module, breaker and dual-input load readiness. A closed main breaker alone does not prove redundancy. | Event-driven state evaluation |
| Post-contingency capacity and headroomSources | S10 | Derived | MW · % | Approved topology, operating limits and actual load | Evaluate surviving source, bus, feeder and load-input limits after one path is lost. For two 800 V / 4000 A buses, nominal per-path power is 3.2 MW; 6.4 MW installed is not 6.4 MW redundant capacity. | 1 s estimate; topology changes revalidated |
| Sample age and validityData quality | D01 | Status | s · quality | Telemetry gateway and source timestamps | Good, stale, missing, out-of-range or substituted flags per measurement. Suppress derived healthy conclusions when any required input is invalid. | Every received sample |
| Time synchronization qualityData quality | D02 | Measured | ms · state | PTP/NTP status and clock offset diagnostics | Clock source, offset and synchronization state for meters, gateways and event recorders. Unsynchronized readings cannot support precise event ordering or small loss calculations. | 10 s health update |
| Calibration and measurement uncertaintyData quality | D03 | Configured | date · % / absolute | Calibration records and complete measurement chain | Sensor/meter identification, range, accuracy, calibration date and due date. Include voltage-divider and current-sensor uncertainty when judging small changes or calculated losses. | Calibration / engineering record update |
| Acquisition and historian configurationData quality | D04 | Configured | S/s · Hz · s | Meter and historian configuration | Acquisition sample rate, analog bandwidth, filters, averaging window, dashboard refresh and retention. These are distinct; slow polling cannot reconstruct fast electrical transients. | Configuration change control |
| Communications and sensor availabilityData quality | D05 | Status | online / total · ms | Gateway diagnostics and expected-device inventory | Expected versus reporting channels, link latency, packet loss and gateway state. Coverage must be calculated against the configured inventory, not only devices that happen to report. | 2 s status update |
| Phase-to-neutral RMS voltageAC voltage | AC-V01 | Measured | V RMS | Three isolated AC voltage channels | Total true-RMS L1-N, L2-N and L3-N voltages for a configured three-phase four-wire wye system. Profiles use 480/√3 V at 60 Hz or 400/√3 V at 50 Hz; line-to-neutral values are not assumed identical. | Local cycle aggregates; 2 s display |
| Line-to-line RMS voltageAC voltage | AC-V02 | Measured | V RMS | Synchronized phase-voltage channels | RMS of L1-L2, L2-L3 and L3-L1 differential waveforms, including modeled harmonics. Under unbalance, calculate each line voltage from its actual phase waveforms rather than multiplying an average by √3. | Local cycle aggregates; 2 s display |
| Frequency and extremaAC voltage | AC-V03 | Measured | Hz · time | AC power-quality meter / PLL | Measured fundamental frequency with timestamped minimum and maximum over an explicitly defined interval. Frequency and 50/60 Hz belong to the AC-side measurement points, not the internal 800 VDC link. | Native meter frequency interval |
| Phase rotationAC voltage | AC-V04 | Status | sequence | Three-phase voltage phasors | Positive sequence L1 → L2 → L3, reverse sequence or unknown. Keep phase labels and sensor polarity consistent through commissioning; a missing or invalid phase must invalidate the sequence conclusion. | Local phasor update |
| Negative-sequence voltage unbalanceAC voltage | AC-V05 | Derived | % | Synchronized fundamental voltage phasors | 100 × magnitude of negative-sequence voltage / magnitude of positive-sequence voltage. This differs from maximum RMS magnitude deviation from the three-phase mean; label both definitions separately. | Fundamental phasor interval |
| Neutral-to-PE voltageAC voltage | AC-V06 | Measured | V RMS | Additional isolated voltage channel | Neutral-to-protective-earth potential at the monitored AC point, with connection and bandwidth stated. This requires its own measurement channel and is not inferred from phase-voltage unbalance. | If fitted: local RMS aggregate |
| Phase RMS currentAC current | AC-I01 | Measured | A RMS | Three suitable CTs or isolated current sensors | Total true-RMS current per phase, including harmonic components. Current-sensor ratio, polarity, bandwidth, burden and saturation performance must match the application. | Local cycle aggregates; 2 s display |
| Neutral RMS currentAC current | AC-I02 | Measured | A RMS | Neutral current sensor; synchronized phasor estimate optional | Neutral current includes phase unbalance and triplen harmonics. It can be measured directly or derived by summing the three instantaneous phase currents, and the display should say which. | Local cycle aggregates; 2 s display |
| Negative-sequence current unbalanceAC current | AC-I03 | Derived | % | Synchronized fundamental current phasors | 100 × negative-sequence current magnitude / positive-sequence current magnitude. Suppress ratios at insufficient current and distinguish sequence unbalance from simple phase-current magnitude spread. | Fundamental phasor interval |
| Voltage and current crest factorsAC current | AC-I04 | Derived | ratio | Time-aligned waveform samples | Absolute waveform peak divided by total RMS over the same capture interval. A distorted waveform may exceed the sinusoidal √2 ratio. Current crest factor is undefined on the unloaded bypass. | Native waveform interval |
| Voltage/current phasorsAC current | AC-I05 | Derived | V · A · degrees | Fundamental-frequency phasor estimator | Per-phase fundamental RMS magnitude and phase angle on a common reference. Current displacement from its own voltage establishes fundamental lead/lag; phasors do not depict total harmonic distortion. | Synchronized fundamental intervals |
| Residual / protective-earth currentAC current | AC-I06 | Status | mA RMS · bandwidth | Dedicated residual-current sensor, if fitted | Residual current measured around all live conductors is separate from load neutral current. Converter loads require a sensor suited to the possible AC/DC components. Preserve sensor type and bandwidth. | If fitted |
| AC active powerAC power & energy | AC-P01 | Measured | kW | Synchronized multiphase power meter | Mean instantaneous voltage × current per phase, summed for total power. Includes real harmonic power where both voltage and current harmonics exist. Positive denotes import from source toward the load. | Local waveform aggregate; 2 s display |
| Apparent powerAC power & energy | AC-P02 | Derived | kVA | Synchronized RMS voltage/current meter | This dashboard defines total apparent power as the arithmetic sum of per-phase Vrms × Irms. Other effective-apparent-power conventions exist; preserve the meter definition when integrating real equipment. | Same interval as active power |
| Fundamental reactive power Q1AC power & energy | AC-P03 | Derived | kvar | Fundamental voltage/current phasors | Sum of per-phase V1 × I1 × sin(displacement angle). Positive is lagging. Q1 excludes harmonic and distortion contributions; do not assume kVA² = kW² + Q1² under distorted conditions. | Fundamental phasor interval |
| True power factorAC power & energy | AC-P04 | Derived | ratio | AC active and apparent power | True PF = active power / apparent power using the stated total-kVA convention. Includes waveform distortion effects and is undefined when the monitored bypass carries zero apparent power. | Same interval as power |
| Displacement power factorAC power & energy | AC-P05 | Derived | ratio · lead/lag | Fundamental voltage/current phasors | Cosine of the fundamental voltage-current displacement angle per phase. Total DPF here is total fundamental active power / summed fundamental apparent power. It is distinct from true PF on nonlinear loads. | Fundamental phasor interval |
| AC imported and exported energyAC power & energy | AC-P06 | Measured | kWh | Bidirectional AC energy registers | Accumulate positive and negative active energy separately; net energy is import minus export. Totals derived from other meters are not billing-grade registers. | Native registers; 1 min history |
| Rolling demand and peak demandAC power & energy | AC-P07 | Derived | kW · time | Meter or synchronized historian | Rolling 15-minute average active power evaluated at 5-minute sample boundaries, plus its maximum over the stated history window. Per-path peaks are not added unless their demand intervals coincide. | 5 min sample boundaries |
| Voltage THD-FAC harmonics | AC-H01 | Derived | % | Harmonic analyzer with defined order range | 100 × root-sum-square voltage RMS in harmonic orders 2–50 / fundamental voltage RMS, separately by phase. This excludes interharmonics and components above order 50; it is not a universal compliance verdict. | Specified harmonic analysis window |
| Current THD-FAC harmonics | AC-H02 | Derived | % | Harmonic current analyzer and suitable sensors | 100 × root-sum-square current RMS in orders 2–50 / fundamental current RMS. High THD at light load needs context. THD is undefined on the unloaded bypass and must not be substituted for TDD. | Specified harmonic analysis window |
| Individual voltage/current harmonicsAC harmonics | AC-H03 | Measured | % fundamental · V · A | Synchronized voltage/current harmonic analyzer | Per-phase magnitude and phase for each harmonic order, with percent values referenced to that phase’s fundamental, across orders 2 through 50. | Native spectral window and grouping |
| Total demand distortion TDDAC harmonics | AC-H04 | Derived | % | Harmonic current plus configured demand-current basis | 100 × harmonic current RMS / maximum-demand fundamental current IL. Initially unavailable until a valid IL is configured. A configured IL, a snapshot value or an arbitrary current-THD threshold does not establish IEEE 519 compliance. | Harmonic interval; demand basis under change control |
| InterharmonicsAC harmonics | AC-H05 | Status | V / A · Hz | Compatible interharmonic analyzer, if fitted | Components between integer harmonics require suitable spectral grouping, windowing and instrument capability. A zero placeholder must not imply that interharmonics are absent. | If fitted |
| Conducted components from 2–150 kHzAC harmonics | AC-H06 | Status | V / A · kHz | Suitable wideband analyzer and probes, if fitted | High-frequency conducted components require defined bandwidth, grouping, transducers and measurement methods. An orders-2–50 spectrum does not establish coverage of the 2–150 kHz band. | If fitted |
| Voltage sagAC events & flicker | AC-Q01 | Measured | % nominal · ms · phase | Locally triggered power-quality event recorder | Store residual RMS voltage, affected phases, start/end time, duration and threshold basis. | Local event detection and retained capture |
| Voltage swellAC events & flicker | AC-Q02 | Measured | % nominal · ms · phase | Locally triggered power-quality event recorder | Store elevated RMS voltage, event duration, affected phases and synchronized waveform/envelope. Compare to the configured nominal system voltage and documented operational threshold. | Local event detection and retained capture |
| Voltage interruptionAC events & flicker | AC-Q03 | Measured | % nominal · ms · location | Locally triggered voltage recorder | Record residual voltage, affected measurement point and duration. An interruption on an idle bypass source is distinct from loss of the inverter output or a load outage. | Local event detection and retained capture |
| Oscillatory / impulsive transientAC events & flicker | AC-Q04 | Measured | V peak · µs / ms | Appropriate high-speed transient recorder | Instantaneous peak voltage, polarity, ringing frequency and duration from an adequately sampled capture. A transient peak is not an RMS residual percentage. | Hardware-triggered high-speed acquisition |
| Correlated input/output waveformsAC events & flicker | AC-Q05 | Measured | V · A · ms | Time-synchronized upstream/downstream event recorders | Compare disturbance timing at the UPS input, bypass and inverter output. Retain mode, pre/post-trigger windows and clock uncertainty. A maintained output in one event does not prove equipment ride-through or transfer performance. | Local triggered buffers with synchronized clocks |
| Short-term flicker PstAC events & flicker | AC-Q06 | Measured | index · 10 min | Compatible IEC flickermeter | Short-term flicker severity from a completed 10-minute instrument interval. Pst cannot be calculated from a short snapshot waveform or a simple voltage-RMS spread. | Completed 10 min intervals |
| Long-term flicker PltAC events & flicker | AC-Q07 | Derived | index · 2 h | Twelve valid consecutive Pst values | Cube root of the mean of the cubes of 12 consecutive 10-minute Pst values. Retain all interval timestamps and validity. | Trailing 12 completed 10 min intervals |
| Rapid voltage changesAC events & flicker | AC-Q08 | Status | % nominal · time | Compatible local RVC detector, if fitted | Identify rapid changes in RMS voltage using the adopted measurement method, thresholds, hysteresis and event flags. Sag/swell examples do not by themselves provide RVC coverage. | If fitted |
| UPS mode and source stateAC system & data | AC-S01 | Status | state · time | UPS controller and independent position feedback | Normal double conversion, static bypass, battery operation or maintenance state from the installed system. Read-only: the monitoring system provides no switching commands. | Event-driven controller status |
| Conversion-boundary power and lossAC system & data | AC-S02 | Derived | kW · % | Synchronized AC/DC meters at matching boundaries | Rectifier AC input, 800 VDC link, DC-fed inverter sections, inverter AC output and downstream PDU output. Calculate losses using aligned meters; do not count the same energy at successive boundaries as separate facility load. | Aligned 1 min averages |
| AC ratings and protection metadataAC system & data | AC-S03 | Configured | V · A · kA · curve | Approved device nameplates and coordination study | Continuous limits, CT/PT ratios, short-circuit interrupting/withstand ratings and protection settings. Prospective fault current cannot be inferred from normal operating current. | Engineering change control |
| AC meter quality and commissioning stateAC system & data | AC-S04 | Status | quality · time · date | Meter, gateway and commissioning records | Source timestamp, freshness, missing channels, synchronization, calibration, polarity and instrument-class evidence. A mathematically valid snapshot does not establish real meter availability or calibration. | Every received sample and status change |
| PCC and assessment basisAC system & data | AC-S05 | Configured | configuration · evidence | Approved connection study and measurement plan | Identify the actual point of common coupling, demand-current IL basis, fault-level basis and applicable measurement duration/statistics. Operational thresholds provide advisories only; no IEEE 519 or IEC compliance pass is implied. | Engineering assessment; not an instantaneous reading |
| Bypass synchronization and transfer permissiveAC system & data | AC-S06 | Status | V · Hz · degrees · state | UPS controller and synchronized source/output measurements | Retain voltage, frequency and phase-angle differences plus manufacturer-reported transfer permitted/inhibited. An energized bypass alone does not prove availability for a safe transfer. | Controller status and native synchronism intervals |
99 matching definitions · Three-phase AC distribution + 800 VDC UPS link · Independent A/B
Which measurements apply depends on the sensors fitted at a given site. Cadences are design targets.
Technical references
Standards and primary technical references behind the measurement design
The design uses configurable three-phase AC profiles and an assumed 800 V two-wire floating UPS DC link. Voltage class, grounding, ratings, sensor selection and operating limits are mapped to the actual installation. References inform the design: they do not certify this demonstration, and listing one does not imply a partnership or an endorsement.- NVIDIA · 800 VDC data-center architecture Architecture context for the illustrative 800 V pole-to-pole system; not a site-specific electrical design.
- Bender · ISOMETER iso685 Insulation monitoring, system capacitance, connection monitoring and self-test for unearthed AC/DC systems.
- Bender · Residual-current measurement principles Explains DC-sensitive residual monitoring. Grounded-system RCM guidance does not replace an IMD on this floating IT example.
- Yokogawa · WT5000 power measurement Reference for synchronized voltage, current and power acquisition, DC accuracy and waveform bandwidth; no specific installed instrument is implied.
- IEC 61000-4-30:2025 · PQ measurement methods The current IEC measurement-method framework. Method classes and documented instrument evidence are separate from operating acceptance limits.
- IEEE 519-2022 · Harmonic control at the PCC Steady-state harmonic assessment applies at the identified point of common coupling. A spot THD reading does not establish compliance.
- HIOKI · AC measurement equations Primary definitions for RMS, power, fundamental components, reactive power and unbalance. Meter calculation conventions must be retained.
- Schneider Electric · THD and TDD Distinguishes harmonic distortion denominators and the maximum-demand current used for TDD.
- HIOKI · Flicker measurement settings Instrument settings for Pst observation intervals and the number of Pst intervals used for Plt.
The design uses configurable three-phase AC profiles and an assumed 800 V two-wire floating UPS DC link. Voltage class, grounding, ratings, sensor selection and operating limits are mapped to the actual installation. References inform the design: they do not certify this demonstration, and listing one does not imply a partnership or an endorsement.