SmartDCDC-01 / Data hall 01 / Measurement library217:46:57 ETDemo dataProduct overview

Measurement library

AC power quality and UPS DC monitoring, with how each value is measured.

99 of 99 measurements

99 measurements across 15 disciplines

Measured, derived, status and configured values

Which measurements apply depends on the sensors fitted at a given site. Cadences are design targets.
MeasurementIDTypeUnitInstrumentDefinitionCadence
Pole-to-pole DC voltageVoltageV01MeasuredV DCIsolated DC voltage inputMean voltage between positive and negative conductors at each main bus and feeder. The nominal system value is 800 V pole-to-pole.1 s aggregate; 2 s display
Positive pole to PEVoltageV02MeasuredV DCHigh-impedance isolated voltage inputSigned positive-conductor potential relative to protective earth. On a floating IT system this may drift; it is not a regulated +400 V rail.1 s aggregate; 2 s display
Negative pole to PEVoltageV03MeasuredV DCHigh-impedance isolated voltage inputSigned negative-conductor potential relative to protective earth. Together with positive-to-PE voltage, reveals displacement of the floating system.1 s aggregate; 2 s display
Voltage minimum and maximumVoltageV04MeasuredV DC · timeDC meter extrema registersLowest and highest pole-to-pole voltage in the selected period, with timestamps and the meter aggregation interval. Separate from waveform event extrema.1 s extrema; retained history
Distribution voltage dropVoltageV05DerivedV · %Synchronized upstream/downstream metersUpstream voltage minus feeder-end voltage; percent drop uses upstream voltage. Compare time-aligned readings under stable load and account for meter uncertainty.1 s calculation
Pole-to-earth displacementVoltageV06DerivedV DCSigned pole-to-PE voltage inputsCommon-mode potential = (Vpositive-to-PE + Vnegative-to-PE) / 2. Diagnostic only; a balanced value does not prove healthy insulation.1 s calculation
Signed main-bus currentCurrentI01MeasuredA DCDC-rated Hall, zero-flux or isolated shunt sensorCurrent through each independent bus. Positive denotes source-to-load flow; negative denotes reverse flow. Do not sum outgoing and returning conductor magnitudes as load current.1 s aggregate; 2 s display
Signed feeder currentCurrentI02MeasuredA DCDC sensor at every monitored tap-offBranch current for each rack or zone. Retain the circuit rating and polarity convention alongside the measurement.1 s aggregate; 2 s display
Parallel conductor currentCurrentI03MeasuredA DCIndividual DC sensors on parallel conductorsCurrent in each parallel positive or negative conductor where sensors are fitted. Supports identification of uneven sharing and overloaded individual paths.1 s aggregate
Parallel conductor sharing errorCurrentI04Derived%Time-aligned parallel conductor current inputs100 × maximum absolute deviation from the mean conductor current / absolute mean current, calculated for parallel conductors of the same pole. Suppress near zero load.1 s calculation
Peak current and event timestampCurrentI05MeasuredA · timeDC meter peak register / waveform recorderHighest current with capture interval and timestamp. High-speed event peaks are distinct from peaks of slow display aggregates.Event capture plus 1 s aggregate
Signed DC active powerPower & energyP01MeasuredkWSynchronized DC power meterMean of simultaneous instantaneous voltage × current samples. Positive is import to the load. Mean voltage × mean current is only a steady-state approximation when ripple correlation is negligible.1 s meter aggregate
15-minute rolling demandPower & energyP02DerivedkWMeter or historianAverage imported power over a rolling 15-minute window ending at each 5-minute sample boundary. The dashboard uses rolling demand rather than fixed demand blocks.Recalculate at 5 min sample boundaries
Maximum 15-minute rolling demandPower & energyP03DerivedkW · timeHistorian demand archiveLargest rolling 15-minute demand in the selected period, evaluated at 5-minute sample boundaries, with interval start and end timestamps. Independent per-path maxima must not be added.Evaluate at 5 min sample boundaries
Imported energyPower & energyP04MeasuredkWhDC energy meter import registerTime integral of positive active power. Keep cumulative, interval and daily totals distinct, with reset/rollover handling.1 min history; 2 s display
Exported energyPower & energyP05MeasuredkWhDC energy meter export registerTime integral of negative active power, reported as a positive exported-energy quantity. Do not hide reverse energy inside a net-only register.1 min history; 2 s display
Bus and feeder utilizationPower & energyP06Derived% · A spareCurrent inputs plus approved operating limitsAbsolute current divided by the applicable continuous operating limit. A configured nameplate rating is not automatically the allowable installed operating limit.1 s calculation
Distribution loss and efficiencyPower & energyP07DerivedkW · %Synchronized input/output DC power metersLoss = input power minus summed downstream power, adjusted for storage and other branches. Efficiency = output/input. Flag results below combined meter uncertainty.1 min average
AC-component voltage ripple RMSDC qualityQ01MeasuredV RMSIsolated waveform analyzerRMS of v(t) minus its DC mean. Always retain the measurement bandwidth, window and sample rate; example design band is 10 Hz–20 kHz.1 s result; ≥100 kS/s acquisition
Voltage ripple peak-to-peakDC qualityQ02MeasuredV p-pIsolated waveform analyzerMaximum minus minimum AC-component voltage over the stated capture window and bandwidth. Not interchangeable with RMS ripple.1 s result; ≥100 kS/s acquisition
Voltage ripple factorDC qualityQ03Derived%Ripple RMS and DC voltage inputs100 × AC-component voltage RMS / absolute DC mean voltage, using the same observation interval. State the bandwidth and suppress near zero DC voltage.1 s calculation
AC-component current ripple RMSDC qualityQ04MeasuredA RMS · %DC-capable current sensor plus waveform analyzerRMS of current after removing its DC mean, with declared bandwidth. Relative ripple uses absolute mean current and is invalid near zero current.1 s result; ≥100 kS/s acquisition
Sag, swell and interruption capturesDC qualityQ05MeasuredV · ms · countTriggered voltage/current waveform recorderEvent type, threshold, start time, duration, minimum/maximum and pre/post-trigger waveform. Event duration comes from local fast acquisition, never inferred from 2-second dashboard polling.Hardware-triggered event capture
Voltage slew rateDC qualityQ06DerivedV/msFiltered high-speed voltage waveformMaximum and minimum dV/dt over a specified event window. Derivative results must include sample interval and filtering to avoid presenting noise as a transient.Triggered waveform calculation
Current slew rateDC qualityQ07DerivedA/msFiltered high-speed current waveformMaximum and minimum dI/dt with capture interval, sensor bandwidth and filter settings. Useful for dynamic load and fault-event diagnostics.Triggered waveform calculation
Joint and conductor temperatureThermalT01Measured°CInstalled contact sensors / calibrated IR systemPositive and negative bar joints, terminations and conductor temperatures with location identifiers. IR measurements require valid emissivity and line-of-sight assumptions.5 s acquisition
Local ambient temperatureThermalT02Measured°CAmbient sensor near each monitored enclosureLocal air temperature paired with each thermal zone. Use it to distinguish high room temperature from local connection heating.5 s acquisition
Temperature rise above ambientThermalT03Derived°C riseJoint and matching ambient sensorsJoint temperature minus local ambient temperature using aligned readings. Operating limits depend on the approved equipment, insulation and installation.5 s calculation
Temperature rate of riseThermalT04Derived°C/minTemperature historianSlope over a specified recent window, such as five minutes, with concurrent current/loading trend. A fast rise can matter before an absolute limit is reached.1 min calculation
Connection voltage dropThermalT05MeasuredmVIsolated differential input across instrumented jointSmall differential voltage across a defined connection under load. Measurement must tolerate the bus common-mode voltage and use suitable isolation.1 s aggregate
Estimated connection resistanceThermalT06DerivedµΩJoint mV drop and matching current sensorR = 1000 × joint voltage drop in mV / current in A. Valid only at sufficient, stable current after offset compensation; this is an online estimate, not an offline micro-ohmmeter test.1 min stable-load estimate
Estimated connection heating lossThermalT07DerivedWEstimated joint resistance and RMS currentApproximate resistive loss = I RMS squared × R. With R in µΩ divide by 1,000,000. Distinguish this local estimate from metered whole-path losses.1 min stable-load estimate
System insulation resistanceInsulationG01MeasuredMΩInsulation monitoring device for floating IT DCEffective resistance of the connected active system to PE. Trend each independent bus and retain response time, self-test status and lowest recorded value.Native IMD update; display age explicitly
Pole-specific insulation estimateInsulationG02DerivedMΩCompatible IMD diagnostic registers, if availablePositive-to-PE and negative-to-PE estimates only if the selected IMD provides valid pole-specific data. Never infer an exact insulation resistance from pole voltage alone.Native device update; otherwise N/A
System leakage capacitanceInsulationG03MeasuredµFCompatible IMD capacitance measurementConnected system capacitance to PE. It affects insulation-monitor response and fault behavior; retain the IMD permitted capacitance and response characteristics.Native IMD update
Residual / earth-leakage currentInsulationG04MeasuredmA DC / RMSDC-capable zero-flux residual sensorResidual current around all active conductors, with bandwidth and DC/RMS basis stated. On a floating system this complements the IMD; it does not replace insulation-resistance monitoring.1 s aggregate; local event detection
IMD health and connection statusInsulationG05Statusstate · timeIMD self-test and connection monitoringDevice healthy/fault, test result and measuring-lead continuity. If buses are coupled, coordinate IMDs according to the approved architecture; do not assume independent monitors can operate on one connected system.Device event; 2 s status poll
Located insulation faultInsulationG06Statuscircuit · stateCompatible insulation-fault location systemIdentified feeder, locator confidence/status and event time when a fault-locator is installed. Show Not instrumented if unavailable; residual current alone does not prove the location of an IT insulation fault.Native locator scan / event
Breaker position and trip stateProtectionR01StatusstateIndependent breaker auxiliary/trip contactsClosed, open, tripped or unknown for every main and branch device. Distinguish position feedback from commands and from current flowing through the circuit.Event-driven; 2 s display
Trip cause and sequence of eventsProtectionR02Statuscause · timeProtection relay / trip-unit event recordLatched cause, trip timestamp, operation sequence and captured fault data where supported. Preserve acknowledged versus cleared states and source timestamp quality.Device event; source resolution retained
Protection and trip circuit healthProtectionR03StatusstateTrip-unit diagnostics and supervision contactsTrip-unit healthy, auxiliary supply healthy and trip-circuit continuity where supervised. No status may be labelled healthy when the channel is stale or absent.Device event; 2 s status poll
DC device ratingsProtectionR04ConfiguredV DC · A · kAApproved manufacturer nameplate and coordination studyRated DC voltage/current and applicable interrupting/withstand ratings, with required pole configuration and conditions. These are engineering metadata, not measured fault current or a live safety margin.Engineering change control
Protection and alarm settingsProtectionR05ConfiguredA · V · ms · °C · MΩApproved device settings / alarm configurationPickup, time delay, hysteresis, latching and reset rules, separately identifying hardware protection and dashboard alarms. Example dashboard thresholds are not approved equipment settings.Engineering change control
Fuse, contactor, precharge and SPD healthProtectionR06StatusstateInstrumented auxiliary contacts and controller registersShow each fitted fuse alarm, contactor position, precharge ready/fault and surge protective device condition separately. Use Not instrumented for devices without feedback.Event-driven; 2 s status poll
Arc detection statusProtectionR07Statusstate · timeQualified DC arc detection system, if fittedDetector health and alarm record only where an appropriate detector is installed. An absent alarm, normal bus telemetry or dashboard status cannot establish absence of arcing.Detector event; otherwise Not instrumented
Rectifier module availabilitySourcesS01Statusonline / total · stateRectifier controllerAvailable, failed, standby and current-limited modules, including controller health. Available output capacity must reflect failed modules and operating derating.Event-driven; 2 s poll
Rectifier current sharingSourcesS02DerivedA / module · %Rectifier per-module DC current registersIndividual module output currents and maximum deviation from the mean among active modules. Evaluate at sufficient load and account for differing module ratings.1 s aggregate
Rectifier conversion efficiencySourcesS03Derived%Synchronized AC input and DC output power meters100 × DC output active power / AC input active power over the same interval. AC power quality belongs to the upstream meter view; it is not a DC bus measurement.1 min average
Battery state of chargeSourcesS04Derived%Battery management system estimateBMS-reported remaining charge fraction with data age and BMS estimation quality. State of charge is an estimate, not a direct guarantee of available runtime.Native BMS update; 5 s display
Battery state of healthSourcesS05Derived%Battery management system estimateBMS-reported health using the manufacturer definition and reference capacity. Track test date and estimator availability.Native BMS update
Battery power and discharge limitSourcesS06MeasuredkW · ABMS / DC-DC converter and battery DC meterSigned charge/discharge power and current, permitted discharge power/current, temperature derating and contactor readiness. Show polarity convention explicitly.1 s aggregate; native limit update
Usable battery energy and runtimeSourcesS07DerivedkWh · minBMS, approved reserve policy and load meteringEstimated runtime = bus-side usable energy / protected load × 60. Apply conversion efficiency only if energy is specified upstream of the converter. BMS discharge limits and actual contingency load still apply.5 s estimate
Battery cell and temperature extremaSourcesS08MeasuredV · mV · °CBMS cell-level telemetryLowest/highest cell voltage, cell spread, hottest/coldest temperature and sensor location. Include BMS warning and fault states.Native BMS update; 5 s display
Independent path availabilitySourcesS09StatusA/B stateSource, breaker and distribution status modelAvailability of each complete source-to-load path, including module, breaker and dual-input load readiness. A closed main breaker alone does not prove redundancy.Event-driven state evaluation
Post-contingency capacity and headroomSourcesS10DerivedMW · %Approved topology, operating limits and actual loadEvaluate surviving source, bus, feeder and load-input limits after one path is lost. For two 800 V / 4000 A buses, nominal per-path power is 3.2 MW; 6.4 MW installed is not 6.4 MW redundant capacity.1 s estimate; topology changes revalidated
Sample age and validityData qualityD01Statuss · qualityTelemetry gateway and source timestampsGood, stale, missing, out-of-range or substituted flags per measurement. Suppress derived healthy conclusions when any required input is invalid.Every received sample
Time synchronization qualityData qualityD02Measuredms · statePTP/NTP status and clock offset diagnosticsClock source, offset and synchronization state for meters, gateways and event recorders. Unsynchronized readings cannot support precise event ordering or small loss calculations.10 s health update
Calibration and measurement uncertaintyData qualityD03Configureddate · % / absoluteCalibration records and complete measurement chainSensor/meter identification, range, accuracy, calibration date and due date. Include voltage-divider and current-sensor uncertainty when judging small changes or calculated losses.Calibration / engineering record update
Acquisition and historian configurationData qualityD04ConfiguredS/s · Hz · sMeter and historian configurationAcquisition sample rate, analog bandwidth, filters, averaging window, dashboard refresh and retention. These are distinct; slow polling cannot reconstruct fast electrical transients.Configuration change control
Communications and sensor availabilityData qualityD05Statusonline / total · msGateway diagnostics and expected-device inventoryExpected versus reporting channels, link latency, packet loss and gateway state. Coverage must be calculated against the configured inventory, not only devices that happen to report.2 s status update
Phase-to-neutral RMS voltageAC voltageAC-V01MeasuredV RMSThree isolated AC voltage channelsTotal true-RMS L1-N, L2-N and L3-N voltages for a configured three-phase four-wire wye system. Profiles use 480/√3 V at 60 Hz or 400/√3 V at 50 Hz; line-to-neutral values are not assumed identical.Local cycle aggregates; 2 s display
Line-to-line RMS voltageAC voltageAC-V02MeasuredV RMSSynchronized phase-voltage channelsRMS of L1-L2, L2-L3 and L3-L1 differential waveforms, including modeled harmonics. Under unbalance, calculate each line voltage from its actual phase waveforms rather than multiplying an average by √3.Local cycle aggregates; 2 s display
Frequency and extremaAC voltageAC-V03MeasuredHz · timeAC power-quality meter / PLLMeasured fundamental frequency with timestamped minimum and maximum over an explicitly defined interval. Frequency and 50/60 Hz belong to the AC-side measurement points, not the internal 800 VDC link.Native meter frequency interval
Phase rotationAC voltageAC-V04StatussequenceThree-phase voltage phasorsPositive sequence L1 → L2 → L3, reverse sequence or unknown. Keep phase labels and sensor polarity consistent through commissioning; a missing or invalid phase must invalidate the sequence conclusion.Local phasor update
Negative-sequence voltage unbalanceAC voltageAC-V05Derived%Synchronized fundamental voltage phasors100 × magnitude of negative-sequence voltage / magnitude of positive-sequence voltage. This differs from maximum RMS magnitude deviation from the three-phase mean; label both definitions separately.Fundamental phasor interval
Neutral-to-PE voltageAC voltageAC-V06MeasuredV RMSAdditional isolated voltage channelNeutral-to-protective-earth potential at the monitored AC point, with connection and bandwidth stated. This requires its own measurement channel and is not inferred from phase-voltage unbalance.If fitted: local RMS aggregate
Phase RMS currentAC currentAC-I01MeasuredA RMSThree suitable CTs or isolated current sensorsTotal true-RMS current per phase, including harmonic components. Current-sensor ratio, polarity, bandwidth, burden and saturation performance must match the application.Local cycle aggregates; 2 s display
Neutral RMS currentAC currentAC-I02MeasuredA RMSNeutral current sensor; synchronized phasor estimate optionalNeutral current includes phase unbalance and triplen harmonics. It can be measured directly or derived by summing the three instantaneous phase currents, and the display should say which.Local cycle aggregates; 2 s display
Negative-sequence current unbalanceAC currentAC-I03Derived%Synchronized fundamental current phasors100 × negative-sequence current magnitude / positive-sequence current magnitude. Suppress ratios at insufficient current and distinguish sequence unbalance from simple phase-current magnitude spread.Fundamental phasor interval
Voltage and current crest factorsAC currentAC-I04DerivedratioTime-aligned waveform samplesAbsolute waveform peak divided by total RMS over the same capture interval. A distorted waveform may exceed the sinusoidal √2 ratio. Current crest factor is undefined on the unloaded bypass.Native waveform interval
Voltage/current phasorsAC currentAC-I05DerivedV · A · degreesFundamental-frequency phasor estimatorPer-phase fundamental RMS magnitude and phase angle on a common reference. Current displacement from its own voltage establishes fundamental lead/lag; phasors do not depict total harmonic distortion.Synchronized fundamental intervals
Residual / protective-earth currentAC currentAC-I06StatusmA RMS · bandwidthDedicated residual-current sensor, if fittedResidual current measured around all live conductors is separate from load neutral current. Converter loads require a sensor suited to the possible AC/DC components. Preserve sensor type and bandwidth.If fitted
AC active powerAC power & energyAC-P01MeasuredkWSynchronized multiphase power meterMean instantaneous voltage × current per phase, summed for total power. Includes real harmonic power where both voltage and current harmonics exist. Positive denotes import from source toward the load.Local waveform aggregate; 2 s display
Apparent powerAC power & energyAC-P02DerivedkVASynchronized RMS voltage/current meterThis dashboard defines total apparent power as the arithmetic sum of per-phase Vrms × Irms. Other effective-apparent-power conventions exist; preserve the meter definition when integrating real equipment.Same interval as active power
Fundamental reactive power Q1AC power & energyAC-P03DerivedkvarFundamental voltage/current phasorsSum of per-phase V1 × I1 × sin(displacement angle). Positive is lagging. Q1 excludes harmonic and distortion contributions; do not assume kVA² = kW² + Q1² under distorted conditions.Fundamental phasor interval
True power factorAC power & energyAC-P04DerivedratioAC active and apparent powerTrue PF = active power / apparent power using the stated total-kVA convention. Includes waveform distortion effects and is undefined when the monitored bypass carries zero apparent power.Same interval as power
Displacement power factorAC power & energyAC-P05Derivedratio · lead/lagFundamental voltage/current phasorsCosine of the fundamental voltage-current displacement angle per phase. Total DPF here is total fundamental active power / summed fundamental apparent power. It is distinct from true PF on nonlinear loads.Fundamental phasor interval
AC imported and exported energyAC power & energyAC-P06MeasuredkWhBidirectional AC energy registersAccumulate positive and negative active energy separately; net energy is import minus export. Totals derived from other meters are not billing-grade registers.Native registers; 1 min history
Rolling demand and peak demandAC power & energyAC-P07DerivedkW · timeMeter or synchronized historianRolling 15-minute average active power evaluated at 5-minute sample boundaries, plus its maximum over the stated history window. Per-path peaks are not added unless their demand intervals coincide.5 min sample boundaries
Voltage THD-FAC harmonicsAC-H01Derived%Harmonic analyzer with defined order range100 × root-sum-square voltage RMS in harmonic orders 2–50 / fundamental voltage RMS, separately by phase. This excludes interharmonics and components above order 50; it is not a universal compliance verdict.Specified harmonic analysis window
Current THD-FAC harmonicsAC-H02Derived%Harmonic current analyzer and suitable sensors100 × root-sum-square current RMS in orders 2–50 / fundamental current RMS. High THD at light load needs context. THD is undefined on the unloaded bypass and must not be substituted for TDD.Specified harmonic analysis window
Individual voltage/current harmonicsAC harmonicsAC-H03Measured% fundamental · V · ASynchronized voltage/current harmonic analyzerPer-phase magnitude and phase for each harmonic order, with percent values referenced to that phase’s fundamental, across orders 2 through 50.Native spectral window and grouping
Total demand distortion TDDAC harmonicsAC-H04Derived%Harmonic current plus configured demand-current basis100 × harmonic current RMS / maximum-demand fundamental current IL. Initially unavailable until a valid IL is configured. A configured IL, a snapshot value or an arbitrary current-THD threshold does not establish IEEE 519 compliance.Harmonic interval; demand basis under change control
InterharmonicsAC harmonicsAC-H05StatusV / A · HzCompatible interharmonic analyzer, if fittedComponents between integer harmonics require suitable spectral grouping, windowing and instrument capability. A zero placeholder must not imply that interharmonics are absent.If fitted
Conducted components from 2–150 kHzAC harmonicsAC-H06StatusV / A · kHzSuitable wideband analyzer and probes, if fittedHigh-frequency conducted components require defined bandwidth, grouping, transducers and measurement methods. An orders-2–50 spectrum does not establish coverage of the 2–150 kHz band.If fitted
Voltage sagAC events & flickerAC-Q01Measured% nominal · ms · phaseLocally triggered power-quality event recorderStore residual RMS voltage, affected phases, start/end time, duration and threshold basis.Local event detection and retained capture
Voltage swellAC events & flickerAC-Q02Measured% nominal · ms · phaseLocally triggered power-quality event recorderStore elevated RMS voltage, event duration, affected phases and synchronized waveform/envelope. Compare to the configured nominal system voltage and documented operational threshold.Local event detection and retained capture
Voltage interruptionAC events & flickerAC-Q03Measured% nominal · ms · locationLocally triggered voltage recorderRecord residual voltage, affected measurement point and duration. An interruption on an idle bypass source is distinct from loss of the inverter output or a load outage.Local event detection and retained capture
Oscillatory / impulsive transientAC events & flickerAC-Q04MeasuredV peak · µs / msAppropriate high-speed transient recorderInstantaneous peak voltage, polarity, ringing frequency and duration from an adequately sampled capture. A transient peak is not an RMS residual percentage.Hardware-triggered high-speed acquisition
Correlated input/output waveformsAC events & flickerAC-Q05MeasuredV · A · msTime-synchronized upstream/downstream event recordersCompare disturbance timing at the UPS input, bypass and inverter output. Retain mode, pre/post-trigger windows and clock uncertainty. A maintained output in one event does not prove equipment ride-through or transfer performance.Local triggered buffers with synchronized clocks
Short-term flicker PstAC events & flickerAC-Q06Measuredindex · 10 minCompatible IEC flickermeterShort-term flicker severity from a completed 10-minute instrument interval. Pst cannot be calculated from a short snapshot waveform or a simple voltage-RMS spread.Completed 10 min intervals
Long-term flicker PltAC events & flickerAC-Q07Derivedindex · 2 hTwelve valid consecutive Pst valuesCube root of the mean of the cubes of 12 consecutive 10-minute Pst values. Retain all interval timestamps and validity.Trailing 12 completed 10 min intervals
Rapid voltage changesAC events & flickerAC-Q08Status% nominal · timeCompatible local RVC detector, if fittedIdentify rapid changes in RMS voltage using the adopted measurement method, thresholds, hysteresis and event flags. Sag/swell examples do not by themselves provide RVC coverage.If fitted
UPS mode and source stateAC system & dataAC-S01Statusstate · timeUPS controller and independent position feedbackNormal double conversion, static bypass, battery operation or maintenance state from the installed system. Read-only: the monitoring system provides no switching commands.Event-driven controller status
Conversion-boundary power and lossAC system & dataAC-S02DerivedkW · %Synchronized AC/DC meters at matching boundariesRectifier AC input, 800 VDC link, DC-fed inverter sections, inverter AC output and downstream PDU output. Calculate losses using aligned meters; do not count the same energy at successive boundaries as separate facility load.Aligned 1 min averages
AC ratings and protection metadataAC system & dataAC-S03ConfiguredV · A · kA · curveApproved device nameplates and coordination studyContinuous limits, CT/PT ratios, short-circuit interrupting/withstand ratings and protection settings. Prospective fault current cannot be inferred from normal operating current.Engineering change control
AC meter quality and commissioning stateAC system & dataAC-S04Statusquality · time · dateMeter, gateway and commissioning recordsSource timestamp, freshness, missing channels, synchronization, calibration, polarity and instrument-class evidence. A mathematically valid snapshot does not establish real meter availability or calibration.Every received sample and status change
PCC and assessment basisAC system & dataAC-S05Configuredconfiguration · evidenceApproved connection study and measurement planIdentify the actual point of common coupling, demand-current IL basis, fault-level basis and applicable measurement duration/statistics. Operational thresholds provide advisories only; no IEEE 519 or IEC compliance pass is implied.Engineering assessment; not an instantaneous reading
Bypass synchronization and transfer permissiveAC system & dataAC-S06StatusV · Hz · degrees · stateUPS controller and synchronized source/output measurementsRetain voltage, frequency and phase-angle differences plus manufacturer-reported transfer permitted/inhibited. An energized bypass alone does not prove availability for a safe transfer.Controller status and native synchronism intervals

99 matching definitions · Three-phase AC distribution + 800 VDC UPS link · Independent A/B

Which measurements apply depends on the sensors fitted at a given site. Cadences are design targets.

Technical references

Standards and primary technical references behind the measurement design

The design uses configurable three-phase AC profiles and an assumed 800 V two-wire floating UPS DC link. Voltage class, grounding, ratings, sensor selection and operating limits are mapped to the actual installation. References inform the design: they do not certify this demonstration, and listing one does not imply a partnership or an endorsement.

The design uses configurable three-phase AC profiles and an assumed 800 V two-wire floating UPS DC link. Voltage class, grounding, ratings, sensor selection and operating limits are mapped to the actual installation. References inform the design: they do not certify this demonstration, and listing one does not imply a partnership or an endorsement.