SmartDCDC-01 / Data hall 01 / Protection & alarms217:46:55 ETDemo dataProduct overview

Protection & alarms

2 active alarms
Measurement guide

Insulation, residual current, device status and actionable events.

Critical alarms0No critical condition
Active advisories22 unacknowledged
Breakers closed14/142 mains + 12 feeders in scope
Lowest insulation1.82MΩIMD self-test passedValid

Active conditions

Acknowledging records awareness. The condition stays active.

  • Elevated connection temperature

    Joint J04-A is 61.6 °C, with a 33.2 K rise above local ambient. Review loading and the connection trend, and arrange inspection under the site’s electrical work procedures.

    AdvisoryJ04-A · Inverter 04 · Positive DC tap-off · 17:24 ET

  • Temperature sensor is not reporting

    The last valid J06-B temperature sample is more than 5 minutes old. Current, voltage and breaker telemetry remain available. Thermal condition is unknown until communication is restored.

    AdvisoryJ06-B · Inverter 06 · Temperature channel · 17:36 ET

Insulation & earth monitoring

Floating two-wire system · separate monitors per isolated bus

Pole-to-earth symmetry does not prove good insulation. If A and B became galvanically connected, the insulation monitors would have to be coordinated.
MeasurementBus ABus BUnit
System insulation resistanceInsulation monitor; valid measurement state1.822.36MΩ
Residual current · AC+DC RMSDC-capable zero-flux sensor · DC–1 kHz band14.211.6mA
System leakage capacitanceIMD estimate to protective earth6.86.3µF
IMD self-test / connectionSimulated instrument diagnosticsPassedPassedstatus
Branch fault locatorNo branch-level insulation localizationNot fittedNot fittedstatus

Pole-to-earth symmetry does not prove good insulation. If A and B became galvanically connected, the insulation monitors would have to be coordinated.

Protective device status

Reported state and configured ratings

Main & feeder trip units
Healthy
Last protection trip
None in history
Main contactors
Closed
Precharge sequence
Complete
Surge protection contacts
Healthy
DC arc-fault detection
Not fitted
Breaker interrupting ratingDC voltage and test conditions required
Not configured
Busbar short-circuit withstandNameplate or study input, not a measured current
Not configured

Monitoring thresholds

Monitoring limits, not protective relay or breaker settings

The alarms on this page follow these limits, delays and reset points. They are starting points that need equipment-specific review. Independent protection performs any trip action, and this interface has no switching or trip controls.
Alarm engine
  • Connection temperature≥ 60 °CAdvisory after 30 s · resets below 55 °C
  • Temperature critical≥ 75 °C10 s delay · resets below 70 °C
  • Thermal sample age> 30 sStale until a fresh valid sample arrives
  • Insulation resistance< 0.50 MΩValid IMD result · 10 s delay · resets above 0.60 MΩ
  • Residual AC+DC RMS> 30 mADC–1 kHz · 10 s delay · resets below 25 mA
  • Bus undervoltage< 760 VDC500 ms delay · resets above 770 VDC
  • Bus overvoltage> 840 VDC500 ms delay · resets below 830 VDC
  • Bus loading> 80%60 s delay · resets below 75%

The alarms on this page follow these limits, delays and reset points. They are starting points that need equipment-specific review. Independent protection performs any trip action, and this interface has no switching or trip controls.

Event history

Eastern time

TimeAssetEventState
17:36 ETJ06-BTemperature sensor is not reportingActive
17:24 ETJ04-AElevated connection temperatureActive
16:47 ETBus ACaptured voltage dip · 772.4 V · 12.4 msRecovered
15:41 ETA + BInsulation monitor self-test completedPassed