SmartDCDC-01 / Data hall 01 / Thermal health217:46:55 ETDemo dataProduct overview

Thermal health

2 active alarms
Measurement guide

Find developing hot spots across bus joints and tap-off terminations.

Hottest monitored joint61.6°CJ04-AAdvisory
Maximum temperature rise33.2KAbove paired local ambient
Temperature channels15/161 stale · excluded from aggregates
Highest joint resistance56.9µΩJ04-A · derived, stable load above 50 A

Joint temperature map

Choose a joint to inspect its feeder and connection readings

J06-B has no current temperature reading. Its electrical channels remain available, and the thermal channel is left out of hottest-point and rise calculations.

A Bus A · joints and tap-offs

B Bus B · joints and tap-offs

  • Within limits
  • Thermal warning
  • Critical
  • Unknown / stale

J06-B has no current temperature reading. Its electrical channels remain available, and the thermal channel is left out of hottest-point and rise calculations.

Conductor & ambient

Main bus · positive and negative conductors

MeasurementBus ABus BUnit
Positive conductorMain bus sensor · valid sample44.243.1°C
Negative conductorMain bus sensor · valid sample43.842.8°C
Local ambientAir sensor within each bus enclosure28.428.1°C
Positive conductor riseConductor minus local ambient, derived15.815.0K
Negative conductor riseConductor minus local ambient, derived15.414.7K

Connection health

Combine heat, load and contact voltage drop

Live contact resistance is an estimate with sensor uncertainty and load qualification, not a de-energized four-wire micro-ohmmeter test. Temperature limits need the actual busway and connection specifications.
Thermal channel coverage12 joint + 4 conductor channels across both buses
15/16 in scope
Online resistance estimateDedicated low-level joint voltage measurement / current
R = ΔV / I
Stable-load validity gate|I| must exceed 50 A
Derived
Estimated resistive lossSteady-state estimate for each monitored joint
P = I²R
Hottest-joint rise rateJ04-A · slope over the last 5 minutes
+0.14 K/min
Time to 75 °C critical limitJ04-A · at the present rate of rise, if nothing changes
About 1.5 h

Live contact resistance is an estimate with sensor uncertainty and load qualification, not a de-energized four-wire micro-ohmmeter test. Temperature limits need the actual busway and connection specifications.

Joint diagnostics

Voltage drop is measured directly across each monitored connection

JointLoad currentTemperatureRise5-min rise rateJoint dropR estimateI²R lossStatus
Section 01177.4 A42.5 °C14.1 K+0.02 K/min4.44 mV25.0 µΩ0.79 WNormal
Section 01172.6 A41.8 °C13.7 K+0.02 K/min3.92 mV22.7 µΩ0.68 WNormal
Section 02189.3 A44.8 °C16.4 K+0.02 K/min5.47 mV28.9 µΩ1.04 WNormal
Section 02185.0 A43.2 °C15.1 K+0.02 K/min4.74 mV25.6 µΩ0.88 WNormal
Section 03183.0 A43.3 °C14.9 K+0.02 K/min4.89 mV26.7 µΩ0.89 WNormal
Section 03183.5 A42.9 °C14.8 K+0.02 K/min4.64 mV25.3 µΩ0.85 WNormal
Section 04204.2 A61.6 °C33.2 K+0.14 K/min11.62 mV56.9 µΩ2.37 WAdvisory
Section 04199.9 A46.1 °C18.0 K+0.02 K/min5.76 mV28.8 µΩ1.15 WNormal
Section 05164.0 A41.8 °C13.4 K+0.02 K/min3.84 mV23.4 µΩ0.63 WNormal
Section 05165.2 A43.7 °C15.6 K+0.02 K/min4.20 mV25.4 µΩ0.69 WNormal
Section 06175.9 A45.4 °C17.0 K+0.02 K/min5.35 mV30.4 µΩ0.94 WNormal
Section 06174.2 A———4.96 mV28.5 µΩ0.86 WTemp unknown

12 connections in scope · Rate is the 5-minute temperature slope · R and loss are derived