SmartDCAC power quality
Measure the supply. See what reaches the load.
Utility incomer · Path A · 480/277 V · 60 Hz · Three-phase wye · 3φ 4-wire · Simulated instruments · Read-only
AC distribution path
UPS path A · Meter locations and conversion stages
Click a meter to change the measurement point. This is an illustrative conversion path with no switching controls. The gap between the incomer and the rectifier input is other load fed ahead of the UPS.- DC link800.1VDC+/− bus · UPS interface
- Normal power path
- Bypass energized / unloaded
- No power flowing
Click a meter to change the measurement point. This is an illustrative conversion path with no switching controls. The gap between the incomer and the rectifier input is other load fed ahead of the UPS.
Phase relationships
L1 voltage is the 0° reference. Vector lengths are normalized within the selected quantity.- L1 · 0.0°278.2 V
- L2 · -119.9°277.6 V
- L3 · 120.1°277.8 V
L1 voltage is the 0° reference. Vector lengths are normalized within the selected quantity.
Three-phase metering
RMS values and power at the selected meter
P is active power, S apparent power, Q₁ fundamental reactive power and DPF the fundamental displacement factor. True PF includes distortion. Phase currents are not summed as a load-current total.| Phase | V L–N | I RMS | P | S | Q₁ | True PF | DPF | THD V | THD I |
|---|---|---|---|---|---|---|---|---|---|
| L1 | 278.3 V | 1,165.2 A | 319.4 kW | 324.2 kVA | 54.0 kvar | 0.985 | 0.986 | 1.70% | 3.70% |
| L2 | 277.7 V | 1,153.2 A | 315.4 kW | 320.2 kVA | 53.3 kvar | 0.985 | 0.986 | 1.80% | 3.90% |
| L3 | 277.8 V | 1,150.6 A | 314.9 kW | 319.7 kVA | 53.3 kvar | 0.985 | 0.986 | 1.60% | 3.60% |
| Total | — | — | 949.8 kW | 964.1 kVA | 160.6 kvar | 0.985 | 0.986 | — | — |
P is active power, S apparent power, Q₁ fundamental reactive power and DPF the fundamental displacement factor. True PF includes distortion. Phase currents are not summed as a load-current total.
Supply quality
Line voltages, sequence unbalance and neutral current
- L1–L2
- 481.2V RMS
- L2–L3
- 481.1V RMS
- L3–L1
- 481.8V RMS
Energy & demand
Selected meter · trailing 24 hours
Derived from the DC historian using fixed conversion assumptions, not a metered billing register. These successive meters observe overlapping power flows, so their powers are not added together as separate facility loads.- Imported energy
- 24.03MWh
- Exported energy
- 0.0kWh
- Rolling 15-minute demand
- 945.5kW
- Peak 15-minute demand
- 1,060.8kW
Positive-energy register
Reverse flow recorded separately
5-minute sample boundaries
Highest rolling window in 24 h
Derived from the DC historian using fixed conversion assumptions, not a metered billing register. These successive meters observe overlapping power flows, so their powers are not added together as separate facility loads.